| Specifications: | |
| Peak Sewage Flow: | 2,500 gallons per day |
| Estimated Percolation Rate: | 55 minutes per inch (Class III Soils) |
| Septic Tank: | 5,000 gallon - concrete top seam |
| Treatment Tank: | 3,000 gallon - top seam |
| Pump Chamber: | 2,500 gallon - top seam |
| AdvanTex Module: | AX-20 - three units Modules are time dosed for 30 seconds and rested for 9.5 minutes |
| Disposal Method: | Multiple drainfield configuration that is demand dosed from the pump chamber. |
![]() 2,500 gallon pump station. |
![]() 5,000 gallon top seam septic tank followed by a 3,000 gallon top seam processing tank. |
![]() Contractor laid a 6" gravel pad on top of the septic tank prior to placing the AdvanTex Treatment Modules. |
![]() The AdvanTex Modules set in place. |
![]() We used a conventional pump vault, with standard filter, float tree, and standard pump package. |
![]() We used an Orenco Automatic Distributing Valve, to allow dosing to a single module at a time. |
![]() Dual Panels operate the AdvanTex pump system, as well as the drainfield dosing pumps. |
![]() AdvanTex Control Panel. |
![]() Pump Chamber control panel. |